Installing gas pipe under solid floor   
All,
I am in the process of building an extension, and need to re-route the
gas pipe from the meter box to the boiler. I plan to have a CORGI in to
do the connections at each end, but I really want to do the pipe run
myself as the plumber is very busy at the moment and waiting for him
will hold up the build.

The bit I need advice about is running the pipe below the new solid
floor. Currently, there is a concrete block & beam floor. This will
then be covered with 90mm Celotex, then 65mm screed.I am planning to do
the following. Does anyone have any objections/suggestions?

I want to run the pipe clipped to the concrete block & beams, cut into
the Celotex. Pipe will be 22mm copper, with several solder ring
straight couplers. I will need 1 solder ring 22-15 reducing tee. Some
sort of sleeve where the copper pipe goes through the screed. (I have
some Speedfit conduit which might do the job).

Plumber will pressure test and commission. I have plenty of experience
soldering pipework.

Is this the normal way to run a pipe in a new solid floor?

My biggest (slight) worry is what happens if there is a leak (somehow)
under the concrete floor. The gas could then seep throughout the whole
floor, between the Celotex sheets. Then /if/ there was some kind of
spark, I dread to think what could happen. Am I being over-concerned? I
suppose the probability is pretty small.

Will discuss with the plumber, but want to know the group's (extensive)
collective wisdom. (grovel grovel...)

Thanks for any advice...

Jon.
Date:21 Sep 2005 02:24:28 -0700   Author:  

Re: Installing gas pipe under solid floor   
Tournifreak wrote:

> 
> The bit I need advice about is running the pipe below the new solid
> floor. Currently, there is a concrete block & beam floor. This will
> then be covered with 90mm Celotex, then 65mm screed.I am planning to do
> the following. Does anyone have any objections/suggestions?
> 
> I want to run the pipe clipped to the concrete block & beams, cut into
> the Celotex. Pipe will be 22mm copper, with several solder ring
> straight couplers. I will need 1 solder ring 22-15 reducing tee. Some
> sort of sleeve where the copper pipe goes through the screed. (I have
> some Speedfit conduit which might do the job).


I don't know what the rules are about burying gas pipes in a solid 
floor, but personally I wouldn't feel very comfortable with it.  Is 
there no other potential route, eg up'n over the ceiling, or even boxing 
it in?

If it was a must though, I'd definitely try to run it within ducting, 
enabling a future duff copper pipe to be replaced with minimal 
disruption (maybe using the nifty technique described by SetSquare in a 
reply to a query of mine to enable access to the ends?): 
http://tinyurl.com/awn2j

Another tip would be to ensure that whoever is signing off the 
installation is happy with you running the gas pipes. Technically, a 
CORGI shouldn't sign off pipework done by you (although some will) even 
if it pressure-tests OK, because that's still no guarantee that the 
joints are properly done and durable - as one CORGI pointed out to me 
that a joint assembled with flux alone (ie, the soldering forgotten!) is 
capable of passing a standard test.  So it would be a pity if you had 
your pipe concreted under the floor, and then nobody would agree to pass it!

David
Date:Wed, 21 Sep 2005 10:29:19 GMT   Author:  

Re: Installing gas pipe under solid floor   
On Wed, 21 Sep 2005 10:29:19 GMT, Lobster
 wrote:


>
>Another tip would be to ensure that whoever is signing off the 
>installation is happy with you running the gas pipes. Technically, a 
>CORGI shouldn't sign off pipework done by you (although some will) even 
>if it pressure-tests OK, because that's still no guarantee that the 
>joints are properly done and durable - as one CORGI pointed out to me 
>that a joint assembled with flux alone (ie, the soldering forgotten!) is 
>capable of passing a standard test.  So it would be a pity if you had 
>your pipe concreted under the floor, and then nobody would agree to pass it!


I'm curious as to what pressure would blow flux out of a joint. Would
pressure testing with 10 bar be good enough?

This is something I have to test in the garden! :-)

Mr F.
Date:Wed, 21 Sep 2005 12:18:17 +0100   Author:  

Re: Installing gas pipe under solid floor   
Lobster wrote:

> I don't know what the rules are about burying gas pipes in a solid
> floor, but personally I wouldn't feel very comfortable with it.  Is
> there no other potential route, eg up'n over the ceiling, or even boxing
> it in?


I could run it up to 1st floor then notch the joists, but seems messy
for a new build. If only one could use Speedfit for gas...would be so
much easier because then I could put holes in the centre of each joist.
Very hard with copper though. Underfloor would be by far the least
messy solution, if it is allowed, and is "normal" practice.



> If it was a must though, I'd definitely try to run it within ducting,

What do others think? I don't see how I'd ever be able to replace/fix a
problem with a non-flexible pipe even if it was in a duct. Both ends of
the pipe are would be inside, (gas box is cavity type) and would have
several bends.

Regards,

Jon.
Date:21 Sep 2005 07:46:25 -0700   Author:  

Re: Installing gas pipe under solid floor   
Tournifreak wrote:

> Lobster wrote:
> 
>>I don't know what the rules are about burying gas pipes in a solid
>>floor, but personally I wouldn't feel very comfortable with it.  Is
>>there no other potential route, eg up'n over the ceiling, or even boxing
>>it in?
> 
> 
> I could run it up to 1st floor then notch the joists, but seems messy
> for a new build. If only one could use Speedfit for gas...would be so
> much easier because then I could put holes in the centre of each joist.
> Very hard with copper though. Underfloor would be by far the least
> messy solution, if it is allowed, and is "normal" practice.
> 
> 
> 
>>If it was a must though, I'd definitely try to run it within ducting,
> 
> What do others think? I don't see how I'd ever be able to replace/fix a
> problem with a non-flexible pipe even if it was in a duct. Both ends of
> the pipe are would be inside, (gas box is cavity type) and would have
> several bends.
> 
> Regards,
> 
> Jon.
> 

ISTR that you aren't allowed joints in gas pipes buried under concrete 
floors.  This topic has come up many times before so a good search in 
google groups may be helpful
Date:Wed, 21 Sep 2005 16:13:08 +0100   Author:  

Re: Installing gas pipe under solid floor   

>ISTR that you aren't allowed joints in gas pipes buried under concrete
>floors.  This topic has come up many times before so a good search in
>google groups may be helpful


I couldn't find anything very conclusive when googling for this topic.
In particular, I couldn't find anything about having joints in what is
effectively a very small duct.
Regs are here:
http://www.opsi.gov.uk/si/si1998/19982451.htm

I'm sure this is something which is done all the time, Id just like to
feel a bit more informed before I speak to my plumber about it.

Thanks & regards,

Jon.
Date:21 Sep 2005 09:33:46 -0700   Author:  

Re: Installing gas pipe under solid floor   
Tournifreak wrote:

> All,
> I am in the process of building an extension, and need to re-route the
> gas pipe from the meter box to the boiler. I plan to have a CORGI in to
> do the connections at each end, but I really want to do the pipe run
> myself as the plumber is very busy at the moment and waiting for him
> will hold up the build.
> 
> The bit I need advice about is running the pipe below the new solid
> floor. Currently, there is a concrete block & beam floor. This will
> then be covered with 90mm Celotex, then 65mm screed.I am planning to do
> the following. Does anyone have any objections/suggestions?
> 
> I want to run the pipe clipped to the concrete block & beams, cut into
> the Celotex. Pipe will be 22mm copper, with several solder ring
> straight couplers. I will need 1 solder ring 22-15 reducing tee. Some
> sort of sleeve where the copper pipe goes through the screed. (I have
> some Speedfit conduit which might do the job).
> 
> Plumber will pressure test and commission. I have plenty of experience
> soldering pipework.
> 
> Is this the normal way to run a pipe in a new solid floor?
> 
> My biggest (slight) worry is what happens if there is a leak (somehow)
> under the concrete floor. The gas could then seep throughout the whole
> floor, between the Celotex sheets. Then /if/ there was some kind of
> spark, I dread to think what could happen. Am I being over-concerned? I
> suppose the probability is pretty small.
> 
> Will discuss with the plumber, but want to know the group's (extensive)
> collective wisdom. (grovel grovel...)
> 
> Thanks for any advice...
> 
> Jon.
> 

I recently had to do something similar. When we discussed it with the 
BCO he wouldn't let me run the pipe in the cellotex and insisted it was 
in the screed, because of this we had to put the cellotex below the slab 
and the pipe in the screed on top. Everyone was happy with this solution.
I would recommend using iron pipe wrapped in denso-tape rather than 
copper, if you don't have the threading dies they're available cheaply 
from the usual culprits. Remember that you must sleeve if you're going 
through any structure.

Dave
Date:Wed, 21 Sep 2005 16:43:45 +0000 (UTC)   Author:  

Re: Installing gas pipe under solid floor   
Tournifreak wrote:

> 
> What do others think? I don't see how I'd ever be able to replace/fix a
> problem with a non-flexible pipe even if it was in a duct. Both ends of
> the pipe are would be inside, (gas box is cavity type) and would have
> several bends.


OK, with lots of bends that would be tricky.

Thinking further on this, how about instead of burying it, you form what 
would essentially be a trough or gutter in the screed, following the 
course of where the pipe will run.  You allow for a rebate in the screed 
at the top of the gutter to allow removable pieces of 0.5" WBP plywood 
to be inset, and which will be flush with the screed.

Still don't know if that is compliant with the regs (particularly 
vis-a-vis running pipes in confined spaces) but to me it sounds better 
than burying them!  Hopefully Mr Sirett will be along shortly with the 
definitive response (although - have you tried searching the archives of 
this ng?)

David
Date:Wed, 21 Sep 2005 17:05:06 GMT   Author:  

Re: Installing gas pipe under solid floor   
On Wed, 21 Sep 2005 17:05:06 +0000, Lobster wrote:


> Tournifreak wrote:
>> 
>> What do others think? I don't see how I'd ever be able to replace/fix a
>> problem with a non-flexible pipe even if it was in a duct. Both ends of
>> the pipe are would be inside, (gas box is cavity type) and would have
>> several bends.
> 
> OK, with lots of bends that would be tricky.
> 
> Thinking further on this, how about instead of burying it, you form what 
> would essentially be a trough or gutter in the screed, following the 
> course of where the pipe will run.  You allow for a rebate in the screed 
> at the top of the gutter to allow removable pieces of 0.5" WBP plywood 
> to be inset, and which will be flush with the screed.
> 
> Still don't know if that is compliant with the regs (particularly 
> vis-a-vis running pipes in confined spaces) but to me it sounds better 
> than burying them!  Hopefully Mr Sirett will be along shortly with the 
> definitive response (although - have you tried searching the archives of 
> this ng?)
> 

This type of work is not a common part of my job. 
It may be that others here are more familiar with these aspect of the regs. 

The gas pipe may not go under the footings of a wall unless there is load
protection - i.e. a Lintel above the pipe - I think this is the same for
waste pipes too. 

Gas pipes must not be run in unventilated voids - it is possible that part
of your proposed route violates this requirement? 

Gas pipes must be protected from possible corrosion due to contact with
cement/mortar/plaster. 

Gas pipes must be inspected and tested for gas tightness BEFORE the above
protection is applied. If you are not able to test for tightness (requires
inspecting each joint) then you are not able to install the pipework. 


-- 
Ed Sirett - Property maintainer and registered gas fitter.
The FAQ for uk.diy is at http://www.diyfaq.org.uk 
Gas fitting FAQ  http://www.makewrite.demon.co.uk/GasFitting.html
Sealed CH FAQ http://www.makewrite.demon.co.uk/SealedCH.html
Date:Wed, 21 Sep 2005 20:25:55 +0100   Author:  

Re: Installing gas pipe under solid floor   
Dave wrote:

> Tournifreak wrote:
> > All,
> > I am in the process of building an extension, and need to re-route the
> > gas pipe from the meter box to the boiler. I plan to have a CORGI in to
> > do the connections at each end, but I really want to do the pipe run
> > myself as the plumber is very busy at the moment and waiting for him
> > will hold up the build.
> >
> > The bit I need advice about is running the pipe below the new solid
> > floor. Currently, there is a concrete block & beam floor. This will
> > then be covered with 90mm Celotex, then 65mm screed.I am planning to do
> > the following. Does anyone have any objections/suggestions?
> >
> > I want to run the pipe clipped to the concrete block & beams, cut into
> > the Celotex. Pipe will be 22mm copper, with several solder ring
> > straight couplers. I will need 1 solder ring 22-15 reducing tee. Some
> > sort of sleeve where the copper pipe goes through the screed. (I have
> > some Speedfit conduit which might do the job).
> >
> > Plumber will pressure test and commission. I have plenty of experience
> > soldering pipework.
> >
> > Is this the normal way to run a pipe in a new solid floor?
> >
> > My biggest (slight) worry is what happens if there is a leak (somehow)
> > under the concrete floor. The gas could then seep throughout the whole
> > floor, between the Celotex sheets. Then /if/ there was some kind of
> > spark, I dread to think what could happen. Am I being over-concerned? I
> > suppose the probability is pretty small.
> >
> > Will discuss with the plumber, but want to know the group's (extensive)
> > collective wisdom. (grovel grovel...)
> >
> > Thanks for any advice...
> >
> > Jon.
> >
> I recently had to do something similar. When we discussed it with the
> BCO he wouldn't let me run the pipe in the cellotex and insisted it was
> in the screed, because of this we had to put the cellotex below the slab
> and the pipe in the screed on top. Everyone was happy with this solution.
> I would recommend using iron pipe wrapped in denso-tape rather than
> copper, if you don't have the threading dies they're available cheaply
> from the usual culprits. Remember that you must sleeve if you're going
> through any structure.
>
> Dave


The problem I will have running the gas pipe in the screed is the
underfloor heating pipes which are also in the screed ;-)
Oh well.

I'll talk to the builder, plumber, and possibly BCO.

Out of interest, why would you recommend iron pipe? Copper can be
wrapped in denso tape can't it?

Thanks & regards,
Jon.
Date:21 Sep 2005 12:43:35 -0700   Author:  

Re: Installing gas pipe under solid floor   
Good idea, but will clash with meters and meters of  carefully planned
under-floor heating pipes! ;-)
Date:21 Sep 2005 12:45:17 -0700   Author:  

Re: Installing gas pipe under solid floor   
Tournifreak wrote:

> Dave wrote:
> 
>>Tournifreak wrote:
>>
>>>All,
>>>I am in the process of building an extension, and need to re-route the
>>>gas pipe from the meter box to the boiler. I plan to have a CORGI in to
>>>do the connections at each end, but I really want to do the pipe run
>>>myself as the plumber is very busy at the moment and waiting for him
>>>will hold up the build.
>>>
>>>The bit I need advice about is running the pipe below the new solid
>>>floor. Currently, there is a concrete block & beam floor. This will
>>>then be covered with 90mm Celotex, then 65mm screed.I am planning to do
>>>the following. Does anyone have any objections/suggestions?
>>>
>>>I want to run the pipe clipped to the concrete block & beams, cut into
>>>the Celotex. Pipe will be 22mm copper, with several solder ring
>>>straight couplers. I will need 1 solder ring 22-15 reducing tee. Some
>>>sort of sleeve where the copper pipe goes through the screed. (I have
>>>some Speedfit conduit which might do the job).
>>>
>>>Plumber will pressure test and commission. I have plenty of experience
>>>soldering pipework.
>>>
>>>Is this the normal way to run a pipe in a new solid floor?
>>>
>>>My biggest (slight) worry is what happens if there is a leak (somehow)
>>>under the concrete floor. The gas could then seep throughout the whole
>>>floor, between the Celotex sheets. Then /if/ there was some kind of
>>>spark, I dread to think what could happen. Am I being over-concerned? I
>>>suppose the probability is pretty small.
>>>
>>>Will discuss with the plumber, but want to know the group's (extensive)
>>>collective wisdom. (grovel grovel...)
>>>
>>>Thanks for any advice...
>>>
>>>Jon.
>>>
>>
>>I recently had to do something similar. When we discussed it with the
>>BCO he wouldn't let me run the pipe in the cellotex and insisted it was
>>in the screed, because of this we had to put the cellotex below the slab
>>and the pipe in the screed on top. Everyone was happy with this solution.
>>I would recommend using iron pipe wrapped in denso-tape rather than
>>copper, if you don't have the threading dies they're available cheaply
>>from the usual culprits. Remember that you must sleeve if you're going
>>through any structure.
>>
>>Dave
> 
> 
> The problem I will have running the gas pipe in the screed is the
> underfloor heating pipes which are also in the screed ;-)
> Oh well.
> 
> I'll talk to the builder, plumber, and possibly BCO.
> 
> Out of interest, why would you recommend iron pipe? Copper can be
> wrapped in denso tape can't it?
> 
> Thanks & regards,
> Jon.
> 


In my (very limited) experience I've only ever seen jointed iron in 
concrete floors, not copper. It's much more robust and easy enough to 
work with.

Dave